Location:Home > news > Industry dynamic - Key points of oil replacement in screw refrigeration compressor

Key points of oil replacement in screw refrigeration compressor
Release time:2018-6-8 11:23:23      Number of clicks:1975
I. functions of lubricating oil:
1) dynamic seal is formed between the screw and the compression chamber and the yin-yang screw to reduce the leakage of refrigerant from the high-pressure side to the low-pressure side in the compression process.
2) cool the compressed refrigerant. Oil is sprayed into the compressor to absorb the heat generated by the refrigerant gas during the compression process and reduce the exhaust temperature.
3) oil film is formed between the bearing and the screw to support the rotor and play a lubricating role.
4) transfer the pressure differential force, drive the capacity adjustment system, adjust the position of the tolerance adjustment slider through the action of adding and unloading the electromagnetic valve of the compressor, and realize the capacity adjustment control of the compressor.
5) reduce operating noise
Description:
The inner lubricating oil of compressor is the key to maintain the normal operation of compressor. The problems of general lubricating oil include:
1) foreign matter mixed in, causing lubricating oil pollution and blocking oil filter.
2) high temperature effect leads to deterioration of lubricating oil and loss of lubrication function.
3) water pollution, acidification and erosion of the system motor.
Ii. Testing and replacement of compressor frozen oil:
For the system manufacturer, the testing and replacement cycle of the refrigeration oil is related to the process control of the production process. If the system of the evaporator and condenser and the cleanliness of the piping control is better, then into the compressor of the pollutants is relatively less, detection and maintenance cycle can be relatively longer.
Main monitoring indicators:
1)PH value index: the acidification of lubricating oil will directly affect the service life of compressor motor, so the acidity of lubricating oil should be checked regularly. General lubricants below PH6 must be replaced. If the acidity cannot be checked, the drying filter of the system should be changed regularly to keep the system in a normal state.
2) pollution index: if the pollutant in 100ml frozen oil exceeds 5mg, it is recommended to replace frozen oil.
3) water content: over 100ppm, it needs to be replaced with frozen oil.
Replacement cycle:
Generally, the lubricating oil should be checked or replaced once every 10,000 hours. After the first operation, it is recommended to replace the lubricating oil once and clean the oil filter after 2500 hours. Because the system assembly residue will accumulate in the compressor after the official operation. Therefore, the lubricating oil should be replaced once every 2500 hours (or 3 months). After that, it should be replaced regularly according to the state of system cleanliness. If the system cleanliness is good, it can be replaced every 10,000 hours (or every year).
If the exhaust temperature of the compressor is maintained at high temperature for a long time, the deterioration of the lubricating oil will be rapid, and the chemical properties of the lubricating oil shall be inspected regularly (every 2 months). If periodic inspection is not possible, it can be performed according to the following recommendation table.
Iii. Operation method of freezing oil replacement:
1) replace frozen oil without internal cleaning:
Pump sets, compressor do system refrigerant reclaiming to condenser side action (note the pump set minimum suction pressure not less than 0.5 Kg/cm2G), will be refrigerant compressor, retain some internal pressure as power source, the frozen oil from the Angle of the compressor oil drain valve.
2) replace frozen oil and conduct internal cleaning:
Dumping actions as mentioned above, frozen oil out clean and compressor pressure balance inside and outside, the flange bolts loose with Allen key, oil filter down joints and settle accounts after the orifice flange (flange) or oil level switch, the pollutant removal within the compressor tank clean, and check the oil filter mesh to see if there is any breakage, and the sludge, pollutants, such as blow, or replace a new oil filter, pay attention to change new filter interface nut to tighten, good sealing, prevent leakage; The inner liner of the oil filter joint must be replaced to prevent internal leakage. Other flange gaskets are also recommended for renewal.
Iv. Matters needing attention:
1. Different brands of frozen oil shall not be mixed, especially mineral oil and synthetic ester oil.
2. If different brands of frozen oil are replaced, please be careful to remove the remaining original frozen oil from the system.
3. Some oil products have the characteristics of moisture absorption, so do not expose frozen oil to air for a long time. Install as much as possible to shorten the exposure time, and do a good vacuum operation.
4. If the system had burned compressor motor fault, replace the new machine should pay special attention to remove residual acid system, and seventy-two hours after the debugging is running check frozen oil acidity, recommend replacing the frozen oil, and dry filters, may reduce the acid corrosion. After running for a month or so, retest or replace the frozen oil.
5. If the system accidents have occurred into the water, it is important to pay special attention to remove water clean, in addition to the replacement of frozen oil, paying special attention to the detection of oil acidity, and timely replacement of the new oil and filter drier.
The last one:Problems with evaporator equipment are solved
Next:About the return oil of refrigeration compressor

Return list

Recommended for you

  • Mobile web site

  • The official WeChat

版權所有: 江蘇利邦機電設備有限公司 Copyright ? 2018 蘇ICP備18027510號-1

主站蜘蛛池模板: 国产精品成人亚洲777| 国产sm鞭打折磨调教视频| 成人视频在线观看| 米奇777四色精品人人爽| 亚洲精品中文幕一区二区| 中国国语毛片免费观看视频 | 成人毛片18女人毛片免费| 在线精品国产大象香蕉网 | 醉酒后少妇被疯狂内射视频| 色视频在线观看免费视频| 制服丝袜av无码专区完整版| 色噜噜噜亚洲男人的天堂| 新香蕉少妇视频网站| 欧洲熟妇色xxxx欧美老妇多毛网站| 久久精品2021国产| 中文字幕久久精品波多野结百度 | 国产精品国产三级国av| 亚洲色精品vr一区二区| 亚洲丁香婷婷久久一区二区| 性色做爰片在线观看ww| 国产精品www夜色视频| 亚洲熟妇色自偷自拍另类| 免费无码午夜福利片| 18禁黄无遮挡网站免费| 久久69国产精品久久69软件| 日韩成视频在线精品| 久久久久久亚洲精品a片成人| 亚洲爆乳aaa无码专区| 亚欧av无码乱码在线观看性色| 久久精品人人槡人妻人| 精品国产乱码久久久久久婷婷| 精品无人区卡一卡二卡三乱码| 午夜裸体性播放| 乱人伦人妻中文字幕在线 | 秋霞午夜成人鲁丝片午夜精品| 精品国产不卡在线观看免费 | 亚洲精品无码专区久久久| 久9视频这里只有精品| 国产精品成人永久在线| 国产剧情无码播放在线观看| 中文字幕精品亚洲人成在线|